constraints, the heights of the bars given by the algorithm in one of the simulations were used, and the dynamic analysis was performed again, comparing the optimized top displacement with the displacement in the top without optimization. The results are shown in Fig. 9. It is important to emphasize that in addition to having managed to bring the building to a maximum displacement value within the acceptable limit in the standard (it reduced from 0.38m to 0.24m), the concrete volume of the structure was also reduced.

Figure 8: Convergence curve of Scenario 1.

Figure 9: Displacement on top of optimized structure

Scenario 2 In this scenario, a TMD was inserted at the top of the structure, connected to node 183 of the structural model. This scenario presents the classic vibration control solution with TMD, by adding one more DOF to the structure. The definition of the location of the energy dissipator is due to the fact that the building's first vibration mode generates greater movements on higher floors. Different from scenario 1, scenario 2 has two more design variables, which are TMD stiffness and damping. All other considerations are identical to scenario 1. The TMD’s mass was adopted as 3% of the structure mass as